Application planning
3.2 Restrictions compared to the S7-1500 automation system
S7-1500R/H redundant system
52
System Manual, 10/2018, A5E41814787-AA
Software restrictions
Table 3- 4
Software restrictions
Function
Restriction
Instructions
Not supported, restrictions for specific instructions: You can
find additional information in the section Restrictions
(Page 150).
Display: "Modules" menu command
Not supported
Firmware update
Firmware update via accessible devices is not supported.
Hardware detection in STEP 7 (read
out configuration)
Not supported
HMI tags
The direct entry of tags on the HMI device is only possible in
the RUN-Solo system state.
I-device
Cannot be used as I-device
1)
IRT
Not supported
Configured connections
Connection type not support for communication connection.
Only programmed connections are supported.
Motion Control
Motion Control functions are not supported in the CPUs
MRPD
Not supported
Multiuser Engineering
Not supported
Online functions
•
Download not possible in the RUN-Redundant system
state
•
SIMATIC Automation Tool (SAT tool) not supported
OPC UA
OPC UA (server and client) not supported
PID controller
Compact PID controllers not supported:
•
PID_Compact
•
PID_3Step
•
PID_Temp
Only the PID basic functions are supported. The PID basic
functions can only be commissioned online in the RUN-Solo
system state.
Protection functions
Not supported: Copy protection
Secure OUC
Not supported as certificate management is not possible for
the R/H CPUs:
If you have enabled Secure OUC, you can compile and load
the user program but cannot add certificates to the R/H
CPUs.
PROFINET send clock
1 ms only
Shared Device
Not supported
SIMATIC ProDiag
Not supported
S7 routing
No S7 routing between PROFINET interface X1 and
PROFINET interface X2 of the R/H CPUs
Summary of Contents for Simatic S7-1500H
Page 1: ......