Mounting dimensions for the S7-1200 devices
$
$
$
%
%
%
%
$
Table 3- 1
Mounting dimensions (mm)
S7-1200 Devices
Width A
Width B
CPU 1211C and CPU 1212C
90 mm
45 mm
CPU
CPU 1214C
110 mm
55 mm
Digital 8 and 16 point
Analog 2, 4, and 8 point
Thermocouple 4 and 8 point
RTD 4 point
45 mm
22.5 mm
Digital DQ 8 x Relay (Changeover)
70
22.5
Signal modules
Analog 16 point
RTD 8 point
70 mm
35 mm
CM 1241 RS232, CM 1241 RS485 and CM 1241 RS422/485
CM 1243-5 PROFIBUS master and
CM 1242-5 PROFIBUS slave
CM 1242-2 AS-i Master
CP 1242-7 GPRS
30 mm
15 mm
Communication
interfaces
TS AdapterIE Basic
60 mm
1
15 mm
1
Because you must install a TS Adapter modular with the TS Adapter, the total width ("width A") is 60 mm.
Each CPU, SM, CM, and CP supports mounting on either a DIN rail or on a panel. Use the
DIN rail clips on the module to secure the device on the rail. These clips also snap into an
extended position to provide screw mounting positions to mount the unit directly on a panel.