Installation Guidelines
3.5.4
Shielding Cables
Shielding is a measure to weaken (attenuate) magnetic, electric or electromagnetic interference
fields.
Interference currents on cable shields are discharged to ground over the shield bar which has a
conductive connection to the housing. So that these interference currents do not become a source
of interference in themselves, a low-resistance connection to the protective conductor is of special
importance.
Use only cables with shield braiding if possible. The effectiveness of the shield should be more
than 80%. Avoid cables with foil shielding since the foil can easily be damaged by tension and
pressure; this leads to a reduction in the shielding effect.
As a rule, you should always shield cables at both ends. Only shielding at both ends provides good
suppression in the high frequency range.
As an exception only, you can connect the shielding at one end. However, this attenuates only the
lower frequencies. Shielding at one end can be of advantage in the following cases:
•
If you cannot run an equipotential bonding conductor
•
If you are transmitting analog signals (e.g. a few microvolts or microamps)
•
If you are using foil shields (static shields).
Always use metallic or metalized connectors for data lines for serial connections. Secure the shield
of the data line at the connector housing. Do
not connect the shield to the PIN1 of the connector
strip!
In the case of stationary operation, we recommend that you insulate the shielded cable without
interruption and connect it to the shield/protective ground bar.
Note
If there are potential differences between the earthing points, a compensating current
can flow over the shielding that is connected at both ends. In this case, connect an
additional equipotential bonding conductor.
EWA 4NEB 811 6130-02b
3-45
Summary of Contents for SIMATIC S5-115U
Page 6: ...EWA 4NEB 811 6130 02b ...
Page 16: ...EWA 4NEB 811 6130 02b ...
Page 18: ...EWA 4NEB 811 6130 02b ...
Page 26: ......
Page 62: ...EWA 4NEB 811 6130 02b ...
Page 64: ...EWA 4NEB 811 6130 02b ...
Page 67: ......
Page 74: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 114: ...EWA 4NEB 811 6130 02b ...
Page 280: ...EWA 4NEB 811 6130 02b ...
Page 372: ...EWA 4NEB 811 6130 02b ...
Page 432: ...EWA 4NEB 811 6130 02b ...
Page 442: ......
Page 528: ...EWA 4NEB 811 6130 02b ...
Page 590: ......
Page 591: ......
Page 592: ......
Page 593: ......
Page 594: ......
Page 600: ...EWA 4NEB 811 6130 02b ...
Page 602: ...EWA 4NEB 811 6130 02b ...
Page 604: ...EWA 4NEB 811 6130 02b ...
Page 624: ...EWA 4NEB 811 6130 02b ...
Page 632: ...EWA 4NEB 811 6130 02b ...
Page 644: ...EWA 4NEB 811 6130 02b ...
Page 646: ...EWA 4NEB 811 6130 02b ...
Page 652: ...EWA 4NEB 811 6130 02b ...
Page 654: ...EWA 4NEB 811 6130 02b ...
Page 660: ...EWA 4NEB 811 6130 02b ...
Page 662: ...EWA 4NEB 811 6130 02b ...
Page 666: ...EWA 4NEB 811 6130 02b ...
Page 668: ...EWA 4NEB 811 6130 02b ...
Page 674: ...EWA 4NEB 811 6130 02b ...