Installation Guidelines
S5-115U Manual
3.4.3 Connecting Nonfloating and Floating Modules
The following sections show the special features involved in installations with nonfloating and
floating modules.
Installation with nonfloating modules
In installations with nonfloating modules, the reference potential of the control circuit (M
internal
)
and the load circuits (M
external
) are galvanically isolated.
The reference potential of the control circuit (M
internal
) is at the PE terminal or
and must be
connected to the reference potential of the load circuit via a line to be run externally.
Figure 3.33 shows a simplified representation of an installation with nonfloating modules. The
installation is independent of the grounding concept. The connections for the grounding
measures are therefore
not shown:
Figure 3-33. Simplified Representation of an Installation with Nonfloating Modules
a a a a a a a
a a a a a a a
a a a a a a a
a a a a a a a
a a a a a a a
1L+
a a a a a
a a a a a
a a a a a
a a a a a
a a a a a
1L
-
a a a a a a
a a a a a a
a a a a a a
a a a a a a
a a a a a a
CPU
a a a a
a a a a
a a a a
a a a a
a a a a
DI
a a a a a
a a a a a
a a a a a
a a a a a
a a a a a
DQ
a a a a
a a a a
a a a a
a a a a
a a a a
PS
a a a a a a a
a a a a a a a
a a a a a a a
a a a a a a a
a a a a a a a
2L+
a a a a a
a a a a a
a a a a a
a a a a a
a a a a a
2L
-
a a a a
a a a a
a a a a
a a a a
a a a a
PE
Control power
supply
24 V DC load power
supply
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
External connection for
uniform reference potential
a a a a a
a a a a a
a a a a a
a a a a a
a a a a a
Data
a a a a a
a a a a a
a a a a a
a a a a a
a a a a a
Mint
a a a a a
a a a a a
a a a a a
a a a a a
a a a a a
Uint
a a a a a
a a a a a
a a a a a
a a a a a
a a a a a
Voltage drop on line must not exceed 1 V, otherwise the reference potentials will shift and
result in module failures.
3-40
EWA 4NEB 811 6130-02b
Summary of Contents for SIMATIC S5-115U
Page 6: ...EWA 4NEB 811 6130 02b ...
Page 16: ...EWA 4NEB 811 6130 02b ...
Page 18: ...EWA 4NEB 811 6130 02b ...
Page 26: ......
Page 62: ...EWA 4NEB 811 6130 02b ...
Page 64: ...EWA 4NEB 811 6130 02b ...
Page 67: ......
Page 74: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 114: ...EWA 4NEB 811 6130 02b ...
Page 280: ...EWA 4NEB 811 6130 02b ...
Page 372: ...EWA 4NEB 811 6130 02b ...
Page 432: ...EWA 4NEB 811 6130 02b ...
Page 442: ......
Page 528: ...EWA 4NEB 811 6130 02b ...
Page 590: ......
Page 591: ......
Page 592: ......
Page 593: ......
Page 594: ......
Page 600: ...EWA 4NEB 811 6130 02b ...
Page 602: ...EWA 4NEB 811 6130 02b ...
Page 604: ...EWA 4NEB 811 6130 02b ...
Page 624: ...EWA 4NEB 811 6130 02b ...
Page 632: ...EWA 4NEB 811 6130 02b ...
Page 644: ...EWA 4NEB 811 6130 02b ...
Page 646: ...EWA 4NEB 811 6130 02b ...
Page 652: ...EWA 4NEB 811 6130 02b ...
Page 654: ...EWA 4NEB 811 6130 02b ...
Page 660: ...EWA 4NEB 811 6130 02b ...
Page 662: ...EWA 4NEB 811 6130 02b ...
Page 666: ...EWA 4NEB 811 6130 02b ...
Page 668: ...EWA 4NEB 811 6130 02b ...
Page 674: ...EWA 4NEB 811 6130 02b ...