New properties/functions
3.2 Changes compared to the previous version
SIMATIC PN/CAN LINK
Operating Instructions, 03/2022, A5E39895388-AC
17
•
Check box Block Error passive alarm
When you select this option, the error passive state of the CAN bus is not reported as an
alarm in the diagnostic buffer. The error LED remains off.
(ISO 11898 CAN Layer 2 device: If one of the error counters is above 127, the device goes
into the "Error Passive" state of the CAN bus. The next error is signaled by a "Passive Error
Flag", which consists of 6 recessive bits. This signal does not destroy any other
communication on the bus. The device is fully operational unless an error counter exceeds
255 and the device goes into the "Bus Off" state.)
New data type "Boolean"
The "Boolean" data type is now available for transmit/receive data OD and transmit/receive
messages.
Editable OD table (manually defined object dictionary)
You can find additional information in the section "Handling of the OD table" in the section