Configuration
5.4 Configuring the telecontrol instructions
CP 1242-7
Operating Instructions, 09/2011, C79000-G8976-C247-02
69
Parameter
Data type
Initial value
Description
GPRSmode
UINT
Mode of the CP:
0 = Telecontrol
1 = GPRS direct
TemporaryStation
BOOL
Bit 0: Temporary connection
If this option is selected, the CP only establishes a
temporary connection to send data. Once the frames
have been transferred, the CP terminates the connection
again.
1: activated (temporary connection)
0: deactivated (permanent connection)
SMS_Enabled
BOOL
Bit 1: Allow SMS
Selecting the option allows the S7 station to send SMS
messages.
1: activated (SMS allowed)
0: deactivated (no SMS)
Field for the "SMSC" parameter
In STEP 7, the corresponding data is located in the parameter area "Modem settings".
Table 5- 11 IF_CONF_SMS_Provider
Parameter
Data type
Initial value
Description
Id
UINT
10
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 28
Mode
UINT
Validity (1: permanent, 2: temporary)
SMSProvider
STRING [20]
Node number of the SMS center (SMSC) of the GSM
network provider with which the contract was signed for
this station.
Field for the "PIN" parameter
In STEP 7, the corresponding data is located in the parameter area "Modem settings".
Table 5- 12 IF_CONF_PIN
Parameter
Data type
Initial value
Description
Id
UINT
11
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 16
Mode
UINT
Validity (1: permanent, 2: temporary)
PIN
STRING [8]
PIN of the SIM card inserted in the SIM card
The parameter is not relevant if the PIN was correctly
configured. If the PIN was incorrectly configured, the
correct PIN can be entered.