Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severi-
ty Lev-
els
Signal Ports
±4 kV Line-to-Earth,
±2 kV Line-to-Line
4
DC Power Ports
±2 kV Line-to-Earth,
±1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-Earth,
±2 kV Line-to-Line
4
Signal Ports
10 V
3
D.C Power Ports
10 V
3
AC Power Ports
10 V
3
IEC 61000-4-6
Induced (Con-
ducted) RFI
Earth
Ground Ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure Ports
40 A/m continuous,
1000 A/m for 1 s
DC Power Ports
30% for 0.1 s, 100% for 0.05 s
IEC 61000-4-29
30% for 1 period,
60% for 250 periods
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
100% for 5 periods,
100% for 50 periods
2
Signal Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
DC Power Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
IEC 61000-4-12
Damped
Oscillatory
AC Power Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
Signal Ports
30 V Continuous, 300 V for 1 s
4
IEC 61000-4-16
Mains Frequen-
cy Voltage
DC Power Ports
30 V Continuous, 300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
Signal Ports
2 kVac (Fail-Safe Relay Output)
DC Power Ports
1.5 kVDC
Dielectric
Strength
AC Power Ports
2 kVAC
Signal Ports
5 kV (Fail-Safe Relay output)
DC Power Ports
5 kV
IEC 60255-5
H.V. Impulse
AC Power Ports
5 kV
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
The RUGGEDCOM RS400F meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Description
Test Levels
Enclosure Contact
±8 kV
ESD
Enclosure Air
±15 kV
36
RUGGEDCOM RS400F
Installation Manual, 02/2020, C79000-G8976-1341-04