Certification
6.1.6 RoHS
6.1.6
RoHS
This device is declared by Siemens AG to meet the requirements of the following Ro-
HS (Restriction of Hazardous Substances) directives for the restricted use of certain
hazardous substances in electrical and electronic equipment:
•
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic Informa-
tion Products
A copy of the Material Declaration is available online at
try.siemens.com/cs/ww/en/view/109738831
6.1.7
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
•
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3:
General Requirements
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS400F has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
Test
Description
Test Levels
Severi-
ty Lev-
els
Enclosure
Contact
±8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
±4 kV at 2.5 kHz
DC Power Ports
±4 kV
4
AC Power Ports
±4 kV
4
IEC 61000-4-4
Burst (Fast
Transient)
Earth
Ground Ports
±4 kV
4
RUGGEDCOM RS400F
Installation Manual, 02/2020, C79000-G8976-1341-04
35