AS-i Master Module CP 142-2
6-1
6 Error Indicators on the CP 142-2 / Dealing with Errors
The following table lists the possible causes of errors that can occur when operating the CP 142-2
and how to remedy the problem.
Error
Possible Cause
Remedy
APF indicator lit.
The AS-i power supply unit is not
connected or is defective.
Check the connection of the AS-i power
supply unit; if necessary replace the
power supply unit.
Power requirements of the AS-i
slave too high.
Result: Voltage on the AS-i cable
too low
Check the power requirements of the
AS-i slaves.
Short circuit on the AS-i cable
Check the AS-i cable and the connected
slaves.
SF lights up without pressing the
button.
The CP 142-2 is in the protected
mode and an AS-i configuration
error has occurred (for example
slave failure).
Eliminate the configuration error.
The CP is in the online phase (for
example after an FC “ASI_3422”
call)
Change the CP to the normal mode (FC
call)
The CP is defective. Internal
EEPROM fault
Replace the CP.
SF is lit when the SET button is
pressed.
An AS-i slave with address 0 exists
when there is a change to the
protected mode.
Remove the AS-i slave with address 0
from the AS-i cable.
CER LED is permanently lit.
The CP 142-2 has not yet been
configured.
Configure the CP using the mode button
on the front panel.
A configured AS-i slave has failed
(evaluate “ACTIVE SLAVES”
display).
Replace the defective As-i slave or
configure the CP 142-2 again if the AS-i
slave is not required.
An unconfigured As-i slave was
connected to the AS-i cable.
Remove the As-i slave or reconfigure the
CP 142-2.
An AS-i slave has been connected
whose configuration data (I/O
configuration, ID code) do not
match the values of the configured
slaves.
Check whether the wrong AS-i slave has
been connected. If necessary,
reconfigure the CP 142-2.
CER display flickers, in other
words a configured AS-i slave is
lost sporadically.
Bad contact
Check the electrical connections of the
AS-i slaves.
Interference on the AS-i cable.
Check the correct grounding of the
ET 200X and check the AS-i cable.
Check that the shield of the AS-i power
supply unit is connected correctly.
The CP does not switch from the
configuration mode to the
protected mode.
Button not pressed long enough
Press the button for at least 5 seconds.
An AS-i slave with address 0 is
connected to the AS-i cable. The
CP 142-2 cannot change to the
protected mode as long as this AS-i
slave exists.
Remove the AS-i slave with address 0.
Summary of Contents for SIMATIC NET CP 142-2
Page 3: ...SIMATIC NET CP 142 2 Manual C79000 B8976 C111 02 ...
Page 70: ...B8976111 02 AS i Master Module CP 142 2 7 2 ...
Page 76: ...AS i Master Module CP 142 2 B8976111 02 A 6 ...
Page 78: ...AS i Master Module CP 142 2 B8976111 02 B 2 ...
Page 80: ...AS i Master Module CP 142 2 B8976111 02 C 2 ...
Page 82: ......