B8976111/02
AS-i Master Module CP 142-2
4-4
If an error occurs when executing the function, a “0” is entered in the BIE bit in addition to the
information above in ERROR and STATUS. The BIE bit is scanned differently in LAD and STL user
programs:
±
LAD: Query using the ENO output parameter
±
STL: Direct querying of the BIE bit
Status and error information
The following table lists the possible information in the first word of STATUS depending on DONE and
ERROR.
DONE
ERROR
STATUS Meaning
0
0
8181
H
Job active
1
0
0000
H
Job completed without error
0
1
8090
H
Address in LADDR invalid
0
1
80A0
H
Negative acknowledgment when reading from module
0
1
80A1
H
Negative acknowledgment when writing to module
0
1
80B0
H
Module does not recognize the data record
0
1
80B1
H
Specified data record length incorrect
0
1
80C0
H
Data record cannot be read
0
1
80C1
H
The specified data record is currently being processed
0
1
80C2
H
There is a job bottleneck
0
1
80C3
H
Resources (memory) in use
0
1
80C4
H
Communication error
0
1
8182
H
ID after complete restart (STARTUP=TRUE)
0
1
8184
H
Data type of the RECV formal address incorrect
0
1
8381
H
Slave address incorrect
0
1
8382
H
Slave is not activated (not in LAS )
0
1
8383
H
Error on the AS-Interface
0
1
8384
H
Command not permitted in the current state of the CP
0
1
8385
H
Slave 0 exists
0
1
83A1
H
Slave with address to be modified not found on AS-Interface
0
1
83A2
H
Slave 0 exists
0
1
83A3
H
Slave with new address already exists on AS-Interface
0
1
83A4
H
Slave address cannot be deleted
Summary of Contents for SIMATIC NET CP 142-2
Page 3: ...SIMATIC NET CP 142 2 Manual C79000 B8976 C111 02 ...
Page 70: ...B8976111 02 AS i Master Module CP 142 2 7 2 ...
Page 76: ...AS i Master Module CP 142 2 B8976111 02 A 6 ...
Page 78: ...AS i Master Module CP 142 2 B8976111 02 B 2 ...
Page 80: ...AS i Master Module CP 142 2 B8976111 02 C 2 ...
Page 82: ......