B8976111/02
AS-i Master Module CP 142-2
3-13
Byte
Bit
Variable Name
Data type
Meaning
11
2
6
OB82_HW_INTR_FLT
BOOL
always 0 for the CP 142-2
11
2
7
OB82_RESERVED_3
BOOL
always 0 for the CP 142-2
3.3.2.6 Reading the Diagnostic Data Record DS1
The CP 142-2 continuously updates a delta list containing all the slaves that deviate from the
configuration, in other words, missing, incorrect or not configured (but existing) slaves (each slave is
assigned one bit in the delta list: 0 = no error; 1 = error). This delta list is part of the diagnostic data
record DS1 and you can read it out by calling the operating system function SFC59 (“RD_REC”) in
the interrupt OB (OB82) or at any time in the cyclic program (OB1).
For the CP 142-2, data record DS 1 always has a length of 11 bytes and is structured as follows:
Bytes 0 to 3:
These four bytes contain DS0 and correspond to the local data bytes 8 to 11 in
OB82 (see Section 3.3.2.5)
Byte 4
7
60
H
0
Bit no.
Byte 7
7
0
Fixed value
Byte 8
7
0
Byte 5
00
H
Byte 6
20
H
Slave 7
Slave 0
Byte 9
7
0
Slave 15
Slave 8
Byte 10
7
0
Slave 23
Slave 16
Delta list
Slave 31
Slave 24
Figure 3-4: Content of Data Record 1 Bytes 4 to 10
Summary of Contents for SIMATIC NET CP 142-2
Page 3: ...SIMATIC NET CP 142 2 Manual C79000 B8976 C111 02 ...
Page 70: ...B8976111 02 AS i Master Module CP 142 2 7 2 ...
Page 76: ...AS i Master Module CP 142 2 B8976111 02 A 6 ...
Page 78: ...AS i Master Module CP 142 2 B8976111 02 B 2 ...
Page 80: ...AS i Master Module CP 142 2 B8976111 02 C 2 ...
Page 82: ......