Interface Submodules
13-31
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
13.6.3
Technical Specifications
Technical Specifications
The IF 961-DIO interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
6ES7961-1AA00-0AC0
Dimensions and Weight
Dimensions W x H x D
(mm)
W x H x D (mm)
18.2 x 67 x 97
Weight
0.065 kg
Module-Specific Data
Submodule ID
02
H
Number of inputs
Number of outputs
8
8
Cable length
•
Unshielded
•
Shielded
200 m at 750
µ
s,
600 m at 3 ms delay
time
1000 m
Voltages, Currents, Potentials
Nominal voltage
Load current supply L+
24 VDC
Permissible nominal
voltage range
Load current supply L+
20.4 V to 28.8 V
Reverse polarity protection
No
(fuse)
Current consumption L+
Dependent on wiring
Number of inputs that can
be controlled
simultaneously
8
Number of outputs that can
be controlled
simultaneously
Galvanic isolation
•
In groups of
8
Yes (optocoupler)
2
Permissible potential
differences
•
Between the M
terminals of the groups
•
Between the input
(M terminal) and the
central grounding point
•
Isolation checked with
75 VDC
60 VAC
75 VDC
60 VAC
500 VDC
Supply voltage
Supplied from the
M7-400
programmable
modules or from the
M7-300/400
expansion modules
Current consumption in the
M7-300
(for dimensioning the 24 V
current supply)
0.03 A
Current consumption in the
M7-400
(for dimensioning the 5 V
current supply)
0.085 A
Power losses of the module
2.4 W