RS 485 Repeater
10-6
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Amplification of the Bus Signals
The amplification of the bus signals takes place between the port for bus segment
1 or the PG/OP interface and the port for bus segment 2.
10.4
Technical Specifications
Technical Specifications of the RS 485 Repeater
Technical Specification
Power supply
pp y
•
Rated voltage
24 VDC
g
•
Ripple
20.4 to 28.8 VDC
Current consumption at rated voltage
p
g
•
without node at PG/OP socket
200 mA
•
Node at PG/OP socket (5 V/90 mA)
230 mA
•
Node at PG/OP socket (24 V/100 mA)
200 mA
Isolation
Yes, 500 VAC
Connection of fiber optic cables
Yes, via repeater adapters
Redundancy operation
No
Transmission rate (automatically detected by the repeater)
9.6 kbaud, 19.2 kbaud, 45.45 kbaud,
93.75 kbaud, 187.5 kbaud, 500 kbaud.
1,5 Mbaud. 3 Mbaud,
6 Mbaud, 12 Mbaud
Degree of protection
IP 20
Dimensions W
H
D (in millimeters)
45
128
67 mm
Weight (incl. packaging)
350 g
Pin Assignment of the Sub-D Connector (PG/OP Socket)
View
Pin No.
Signal Name
Designation
1
–
–
2
M24V
Ground 24 V
5
3
RxD/TxD-P
Data line B
9
4
4
RTS
Request To Send
3
8
5
M5V2
Data reference potential (from station)
3
2
7
6
P5V2
Supply plus (from station)
2
1
6
7
P24V
24 V
1
8
RxD/TxD-N
Data line A
9
–
–