Analog Modules
5-16
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Analog Value Representation for Resistance Thermometers Ni x00 Standard
Table 5-18 Analog Value Representation for Resistance Thermometers Ni100, 120, 200, 500, 1000
Ni x00
Standard
Units
Ni x00
Standard
Units
Ni x00
Standard
Units
Standard
in
5
C
(1 Digit =
0.1
5
C)
Deci-
mal
Hexa-
deci-
mal
Standard
in
5
F
(1 Digit =
0.1
5
F)
Deci-
mal
Hexa-
deci-
mal
Standard
in K
(1 Digit =
0.1 K)
Deci-
mal
Hexa-
deci-
mal
Range
> 295.0
32767
7FFFH
> 563.0
32767
7FFFH
> 568.2
32767
7FFF
H
Overflow
295.0
2950
B86
H
563.0
5630
15FE
H
568.2
5682
1632
H
:
:
:
:
:
:
:
:
:
Overrange
250.1
2501
9C5
H
482.1
4821
12D5
H
523.3
5233
1471
H
g
250.0
2500
9C4
H
482.0
4820
12D4
H
523.2
5232
1470
H
:
:
:
:
:
:
:
:
:
Rated range
–60.0
–600
FDA8
H
–76.0
–760
FD08
H
213.2
2132
854
H
–60.1
–601
FDA7
H
–76.1
–761
FD07
H
213.1
2131
853
H
:
:
:
:
:
:
:
:
:
Underrange
–105.0
–1050
FBE6
H
–157.0
–1570
F9DE
H
168.2
1682
692
H
g
< –105.0
–32768
8000
H
< –157.0
–32768
8000
H
< 168.2
32768
8000
H
Underflow
Analog Value Representation for Resistance Thermometers Ni x00 Climatic
Table 5-19 Analog Value Representation for Resistance Thermometers Ni 100, 120, 200, 500, 1000
Ni x00
Climatic
in
5
C
Units
Ni x00
Climatic
in
5
F
Units
Range
in
5
C
(1 Digit =
0.01
5
C)
Decimal
Hexadecimal
in
5
F
(1 Digit =
0.01
5
F)
Decimal
Hexadecimal
Range
> 295.00
32767
7FFF
H
> 325.11
32767
7FFF
H
Overflow
295.00
:
250.01
29500
:
25001
733C
H
:
61A9
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61
H
Overrange
250.00
:
–60.00
25000
:
–6000
61A8
H
:
E890
H
280.00
:
–76.00
28000
:
–7600
6D60
H
:
E250
H
Rated range
–60.01
:
–105.00
–6001
:
–10500
E88F
H
:
D6FC
H
–76.01
:
–157.00
–7601
:
–15700
E24F
H
:
C2AC
H
Underrange
< – 105.00
–32768
8000
H
< – 157.00
–32768
8000
H
Underflow