Measuring Ranges
You set the measuring ranges by means of the measuring range modules on the
module and the “Measuring Type” parameter in STEP 7.
Table 5-55 Measuring Ranges of the SM 431; AI 8 x 14 Bit
Method Selected
Measuring Range
(Type of Sensor)
Measuring Range
Module Setting
Description
U: Voltage
"
80 mV
"
250 mV
"
500 mV
"
1 V
A
You will find the digitized analog
values in Section 5.3.1 in the
voltage measuring range
"
2.5 V
"
5 V
1 to 5 V
"
10 V
2DMU: Current (two-wire
transmitter)
4 to 20 mA
D
To supply these transmitters with
current you must connect 24 V to
the L+ and M front connector
terminals.
You will find the digitized analog
values in Section 5.3.1 in the
current measuring range
4DMU: Current
(four-wire transmitter)
0 to 20 mA
4 to 20 mA
"
20 mA
C
You will find the digitized analog
values in Section 5.3.1 in the
current measuring range
R-4L: Resistors
(four-conductor
connection)
48
150
300
600
6000
A
You will find the digitized analog
values in Section 5.3.1 in the
resistance measuring range
R-3L: Resistors
(three-conductor
connection)
300
600
6000