Planning application
3.2 Mounting location and clearance of charging station
Mobile Panel 277F IWLAN
54
Operating Instructions, 12/2007, A5E01003940-01
Ambient conditions
Permitted range
Comments
Temperature
•
Operation
•
Storage/transport
•
0 to 50 °C
•
–20 to 60 °C
Relative humidity
5 to 85 %,
no condensation
Corresponds to relative humidity, load
degree 2 in accordance with IEC 61131,
part 2
Atmospheric pressure
1.060 hPa to 700 hPa
Corresponds to an elevation of –1,000
to 2,000 m
SO
2
: < 0.5 vpm;
Relative humidity < 60 %, no
condensation
Check: 10 cm
3
/m
3
; 10 days
Pollutant concentration
H
2
S: < 0.1 vpm;
Relative humidity < 60 %, no
condensation
Check: 1 cm
3
/m
3
; 10 days
3.2
Mounting location and clearance of charging station
Selecting a mounting location for the charging station
The charging station is designed for vertical installation.
WARNING
Emergency stop button not effective
If the HMI device is not integrated, the emergency stop button does not function.
The charging station must be installed in either a system area with sufficiently wide WLAN
coverage or a separate service area. If the charging station is in the system and the HMI
device is hooked into the charging station, the emergency stop button must be effective.
To avoid confusion between effective and non-effective emergency stop buttons, only one
integrated HMI device should be freely accessible.
CAUTION
System or machine stop
The HMI device can fall down if it is not securely hooked in. The emergency stop button on
the HMI device can also be triggered unintentionally.
In order to ensure that the HMI device can be hooked in securely, select a vertical surface
or one inclined slightly to the rear as the mounting surface.