Appendix
A.2 System alarms
OP 73micro, TP 177micro (WinCC flexible)
152
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
Meaning of the system alarms
Number Effect/cause
Remedy
10000 The print job could not be started or was canceled
due to an unknown error. Faulty printer setup. Or:
Access to the network printer is not allowed.
Power supply failure during data transfer.
Check the printer settings, cable connections and the
power supply.
Set up the printer once again. Obtain a network printer
authorization.
If the error persists, contact the Hotline!
10001 No printer is installed or a default printer has not
been set up.
Install a printer and/or select it as the default printer.
10002 Overflow of the graphics buffer for printing. Up to
two images are buffered.
Allow sufficient intervals between successive print jobs.
10003 Images can now be buffered again.
-
10004 Overflow of the buffer for printing lines in text mode
(e.g.alarms). Up to 1000 lines are buffered.
Allow sufficient intervals between successive print jobs.
10005 Text lines can now be buffered again.
-
10006 The Windows printing system reports an error.
Refer to the output text and the error ID to
determine the possible causes. Nothing is printed
or the print is faulty.
Repeat the action if necessary.
20010 An error has occurred in the specified script line.
Execution of the script was therefore aborted. Note
the system alarm that may have occurred prior to
this.
Select the specified script line in the configuration.
Ensure that the tags used are of the allowed types.
Check system functions for the correct number and types
of parameters.
20011 An error has occurred in a script that was called by
the specified script.
Execution of the script was therefore aborted in the
called script.
Take the system alarm that may have occurred
prior to this into account.
In the configuration, select the script that has been called
directly or indirectly by the specified script.
Ensure that the tags used are of the allowed types.
Check the system functions for the correct number and
type of parameters.
20012 The configuration data is inconsistent. The script
could therefore not be generated.
Recompile the configuration.
20013 The scripting component of WinCC flexible Runtime
is not correctly installed. Therefore, no scripts can
be executed.
Reinstall WinCC flexible Runtime.
20014 The system function returns a value that is not
written in any return tag.
Select the specified script in the configuration.
Check if the script name has been assigned a value.
20015 Too many successive scripts have been triggered
in short intervals. When more than 20 scripts are
queued for processing, any subsequent scripts are
rejected. In this case, the script indicated in the
alarm is not executed.
Find what is triggering the scripts. Extend the times, e.g.
the polling time of the tags which trigger the scripts.
30010 The tag could not accept the function result, e.g.
when it has exceeded the value range.
Check the tag type of the system function parameter.
30011 A system function could not be executed because
the function was assigned an invalid value or type
in the parameter.
Check the parameter value and tag type of the invalid
parameter. If a tag is used as a parameter, check its
value.
40010 The system function could not be executed since
the parameters could not be converted to a
common tag type.
Check the parameter types in the configuration.