Appendix
A.2 System alarms
OP 73micro, TP 177micro (WinCC flexible)
164
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
Number Effect/cause
Remedy
190102 The area pointer is updated after the cause of the
last error state has been eliminated (return to
normal operation). Parameter type and no.: See
alarm 190100.
-
200000 Coordination is not executed because the address
configured in the controller does not exist/is not set.
Change the address or set up the address in the
controller.
200001 Coordination is canceled because the write access
to the address configured in the PLC is not
possible.
Change the address or set the address in the controller at
an area which allows write access.
200002 Coordination is not carried out at the moment
because the address format of the area pointer
does not match the internal storage format.
Internal fault
200003 Coordination can be executed again because the
last error state is eliminated (return to normal
operation).
-
200004 The coordination may not be executed.
-
200005 No more data is read or written. Possible causes:
•
The cable is defective.
•
The PLC does not respond, is defective, etc.
•
System overload.
Ensure that the cable is plugged in and the controller is
operational.
Restart the system if the system alarm persists.
200100 Coordination is not executed because the address
configured in the controller does not exist/is not set.
Change the address or set up the address in the
controller.
200101 Coordination is canceled because the write access
to the address configured in the PLC is not
possible.
Change the address or set the address in the controller at
an area which allows write access.
200102 Coordination is not carried out at the moment
because the address format of the area pointer
does not match the internal storage format.
Internal fault
200103 Coordination can be executed again because the
last error state is eliminated (return to normal
operation).
-
200104 The coordination may not be executed.
-
200105 No more data is read or written. Possible causes:
•
The cable is defective.
•
The PLC does not respond, is defective, etc.
•
System overload.
Ensure that the cable is plugged in and the controller is
operational.
Restart the system if the system alarm persists.
210000 Jobs are not processed because the address
configured in the controller does not exist/has not
been set up.
Change the address or set up the address in the
controller.
210001 Jobs are not processed because read/write access
to the address configured in the controller is not
possible.
Change the address or set up the address in the
controller in an area which allows read/write access.
210002 Jobs are not executed because the address format
of the area pointer does not match the internal
storage format.
Internal fault
210003 The job buffer is processed again because the last
error status has been eliminated (return to normal
operation).
-