Fail-Safe Modules
7.3 PM-E F pp DC24V PROFIsafe power module
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
91
Diagnostic functions
The table below provides an overview of the diagnostic functions of the PM-E F pp DC24V
PROFIsafe. The diagnostic functions are assigned either to one channel or to the entire
module.
Table 7- 9
Diagnostic functions of the PM-E F pp DC24V PROFIsafe
Diagnostic Function*
Fault
number
LED
Effective Range of
Diagnostics
can be
assigned
parameter
s
Short circuit
1
H
SF
Channel
No
Overtemperature
5
H
SF
Module
No
Internal error
9
H
SF
Module
No
Parameter assignment error
10
H
SF
Module
No
Sensor voltage or load voltage missing
11
H
SF
Module
No
Communication error
13
H
SF
Module
No
Safety-related shutdown
19
H
SF
Channel
No
*: Specially for F-modules; display in
STEP 7
, see "Channel-Specific Diagnostics, Fault Types of Fail-
Safe Modules" table
WARNING
Before acknowledging the short-circuit diagnosis, remedy the respective error and validate
your safety function. To do this, proceed as described in chapter "Fault Diagnostics
Causes of Faults and Corrective Measures
The following table contains the possible causes of the faults described for the individual
diagnostic messages of the PM-E F pp DC24V PROFIsafe and remedies.
Table 7- 10 Diagnostic messages of the PM-E F pp DC24V PROFIsafe, causes of errors and
remedies
Diagnostic
Message
Fault
Detection
Possible Causes
Corrective Measures
Cross-circuit between
P1 and L+
Remedy the cross-circuit and
acknowledge the error within 100 hours
after the error has occurred
Short circuit
For "0"
output signal
only
Internal error
Replace module
Overtemperatur
e
Always
Shutdown due to
violation of upper or
lower temperature limit
value in the module
case
Check load wiring, check ambient
temperature, check whether permissible
output current is exceeded for the
ambient temperature. Once the fault has
been eliminated, the module must be
removed and inserted or the power
switched off and on.