Fail-Safe Modules
7.2 PM-E F pm DC24V PROFIsafe Power Module
ET 200S Distributed I/O System - Fail-Safe Modules
76
Installation and Operating Manual, 08/2008, A5E00103686-07
Diagnostic functions
The table below provides an overview of the diagnostic functions of the PM-E F pm DC24V
PROFIsafe. The diagnostic functions are assigned either to one channel or to the entire
module.
Table 7- 4
Diagnostic functions of the PM-E F pm DC24V PROFIsafe
Diagnostic Function*
Fault
Number
LED
Effective Range of
Diagnostics
Can be
Assigned
Parameter
s
Short circuit
1
H
SF
Channel
No
Overload
4
H
SF
Channel
No
Overtemperature
5
H
SF
Module
No
Wire break
6
H
SF
Channel
Yes
Internal error
9
H
SF
Module
No
Parameter assignment error
10
H
SF
Module
No
Sensor voltage or load voltage missing
11
H
SF
Module
No
Communication error
13
H
SF
Module
No
Safety-related shutdown
19
H
SF
Channel
No
*: Specially for F-modules; display in
STEP 7
, see "Channel-Specific Diagnostics, Fault Types of Fail-
Safe Modules" table
WARNING
Before acknowledging the short-circuit diagnosis, remedy the respective error and validate
your safety function. To do this, proceed as described in chapter "Fault Diagnostics
(Page 43)".