54
Internal Accessories
Undervoltage Release (UVR) Solenoid
CAUTION: Do not attempt to install an accessory with
the breaker “Closed” or “Charged”. Make certain breaker
is “Open” and “Discharged” as shown above. Personal
injury or mechanical damage may occur. Preliminary
installation procedures are outlined on pages 36-37.
Undervoltage Release Kit
Undervoltage Release
The undervoltage release (UVR) trips the SB breaker in accor-
dance with the pick-up and dropout requirements of UL-4.89.
The monitored voltage is normally the voltage on the line side
of the breaker. Available UVR coil ratings are 120, 240. 480.
or 600V ac or 12, 24, 48, or 125V dc. The UVR will instanta-
neously (no intentional delay) trip the breaker when the voltage
drops below the trip value. Tripping can be delayed up to 0.5
seconds by using the external time delay undervoltage acces-
sory with the UVR.
The UVR accessory kit consists of a trip solenoid to trip the
breaker, mounting hardware, and internal wiring . The trip
solenoid is installed on the right side of the front compartment,
behind the trip unit and beneath the reset plate.
Notes:
1.
Wire markings are shown in brackets <like this>.
2.
LT indicates left-top terminal block or secondary con-
nector
If practical, the UVR should be installed prior to the SB breaker
being installed in the switchboard. Before starting the instal-
lation, the breaker should be in the open position and the
stored energy mechanism should be discharged. A drawout
constructed breaker, already installed in the switchboard,
should be placed in the fully withdrawn position to allow
access to the secondary disconnects. If being installed in a
drawout breaker, use access-hole in right side mechanism
assembly.
To install the undervoltage release, first remove the SB
breaker front cover and trip unit, if previously installed (see
page 37).
1 )
Place UVR solenoid beneath breaker reset plate
2 )
Install UVR on top right side of reset mechanism
3 )
Route the UVR solenoid wire leads across the back of the
stored energy mechanism located between the wire
shield and the mid-barrier to the left side of the breaker.
Summary of Contents for SBA 1200
Page 68: ...66 External Accessories Ground Fault Sensing and Relaying Courtesy of NationalSwitchgear com ...
Page 94: ...92 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 95: ...93 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 100: ...98 Courtesy of NationalSwitchgear com ...
Page 101: ...Electrical Diagrams 99 Courtesy of NationalSwitchgear com ...
Page 102: ...100 Electrical Diagrams Courtesy of NationalSwitchgear com ...