Internal Accessories
57
Shunt Trip Schematic Layout
Figure 4.
8.)
Route all wires between the wire shield and mid barrier,
make Sure to route the wires toward the bottom of the
trough, So that the wires fit into the mid barrier trough
(See Figure 4)
9.)
Add cable tie mounts and cable tie as directed in acces-
sory instructions (See Figure 5)
Figure 5.
Figure 6.
10.) Replace trip unit and breaker front cover. being careful
not to pinch wire leads routed to secondary disconnects
or terminal block. (See Figure 6)
11.) Apply the shunt trip accessory label to side of the breaker
cover (see Figure 7) Mark the label that is on the opposite
side of the cover to indicate that the shunt trip has been
installed.
Shunt Trip Ratings
Catalog Number
In-Rush Current (Amperes)
Operating Voltage
SBST12
SBST24
SBST48
SBST125
SBST120
SBST240
SBST480
2.50
1.75
1.10
1.02
.63
.41
.35
12V dc
24V dc
48V dc
125V dc
120V dc
240V dc
480V dc