72
External Accessories
Secondary Disconnects and Control Terminal Blocks
CAUTION: Do not attempt to install an accessory with
the breaker “Closed” or “Charged”. Make certain breaker
is “Open” and “Discharged” as shown above. Personal
injury or mechanical damage may occur.
Secondary Disconnects
Secondary wiring connections to remote locations are made
to “secondary disconnects” on drawout breakers and to
“control terminal blocks” on fixed-mounted breakers. The
secondary disconnects and terminal blocks are located along
the sides of the breakers, as many as two on each side. They
are referenced as left top (LT), left bottom (LB), right top (RT),
and right bottom (RB). Left and right are with respect to the
user facing the breaker. The terminal points of factory installed
internal accessories are identified on page 62. The same
terminal point locations should be used when an accessory is
installed in the field.
Secondary Disconnects terminal points
Control Terminal Block mounted on fixed-mounted breaker.
Control Terminal Blocks
Control terminal blocks provide electrical access to the inter-
nal accessories and trip unit of a fixed-mounted breaker. A
breaker can be equipped with up to four control terminal
blocks, each with 12 terminal points. The terminal blocks
accept #12 AWG user wiring. They are rated for 600 volts
application.
The terminal blocks are designed to be installed along the
sides of the breaker. They must be installed with a terminal
block mount. To install the terminal block assembly(s), attach
them with screws to the breaker as illustrated.
The control terminal blocks are referenced as left-top (LT), left-
bottom (LB), right-top (RT), and right-bottom (RB). Left and
right are with respect to the user facing the breaker. The
recommended terminal points for accessories added in the
field are illustrated below.
NOTE: The addition of terminal blocks to a fixed mounted
circuit breaker adds 1.5 inches to each side or 3 inches
overall.
Wires mounted on terminal block
Summary of Contents for SBA 1200
Page 68: ...66 External Accessories Ground Fault Sensing and Relaying Courtesy of NationalSwitchgear com ...
Page 94: ...92 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 95: ...93 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 100: ...98 Courtesy of NationalSwitchgear com ...
Page 101: ...Electrical Diagrams 99 Courtesy of NationalSwitchgear com ...
Page 102: ...100 Electrical Diagrams Courtesy of NationalSwitchgear com ...