Racking Controls
A built-in, low-force pump handle and two control levers are
used to rack the moveable drawout element between the
connected, test, and withdrawn positions.
Part Two- Manipulating the Moveable Drawout Element
Racking Controls Locations
Directional Shift Lever
The directional shift lever determines the direction the mov-
able drawout element will move when it is racked. The lever
has three positions: racking-out, neutral, and racking-in.
When the lever is in the
racking-out
position (pulled all the
way out), the moveable drawout element may be racked
from the connected position to the test position, and from the
test position to the unlocked position. When the lever is set
in the
neutral
position (located midway between the racking-
in and racking-out positions), the racking pump handle is
disengaged from the racking mechanism. In the
racking-in
position (pushed all the way forward), the moveable drawout
element may be racked from the unlocked position to the test
position, and from the test position to the connected position.