38
Internal Accessories
Preparation For Installation of Electric Motor Operator
CAUTION: Siemens advises that all internal accesso-
ries should be added with the breaker removed from
service and properly secured to a work surface. Do not
attempt to install accessories with the breaker in a
“Closed” or “Charged” position. Personal injury or
mechanical damage may occur.
Accessories
The full family of accessories available for Siemens SB
breakers are presented in this section. The accessories are
divided into two groups: accessories that are installed in the
front compartment of the circuit breaker (Internal Accesso-
ries) and accessories that are installed or used outside of the
front compartment (External Accessories). The External Ac-
cessories are installed on the exterior of the circuit breaker,
on the drawout elements, or at remote locations. When the
installation location is referred to as the “right side” or “left
side,” it is with reference to the user’s right or left side when
facing the front of the breaker.
Components required to access or activate an accessory
such as a switch or indicator at a remote location are
assumed to be user supplied unless otherwise stated.
Group One- Internal Accessories
Secondary connections to remote locations are made to
“secondary disconnects” on drawout breakers and to “con-
trol terminal blocks” on fixed-mounted breakers. The terminal
points for all internal accessories are defined in the External
Accessories section, pages 72-73. Control power connec-
tions for accessories are made through terminal blocks
mounted on the sides of the breaker (see page 72). Drawout
constructed breaker control power connections are made
through secondary disconnects mounted on the stationary
and moving elements.
SB Drawout Breaker Preparation
Installation or removal of the electric motor operator requires
the removal of the left drawout mechanism assembly. Instal-
lation or removal of the undervoltage release solenoid or
shunt trip may require the removal of the right drawout
mechanism assembly. Following are instructions for the
removal and reinstallation of assemblies.
SB Encased Systems Breaker controls and indicators
Summary of Contents for SBA 1200
Page 68: ...66 External Accessories Ground Fault Sensing and Relaying Courtesy of NationalSwitchgear com ...
Page 94: ...92 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 95: ...93 Outline Dimension Drawing 2000A Fixed Mounted Courtesy of NationalSwitchgear com ...
Page 100: ...98 Courtesy of NationalSwitchgear com ...
Page 101: ...Electrical Diagrams 99 Courtesy of NationalSwitchgear com ...
Page 102: ...100 Electrical Diagrams Courtesy of NationalSwitchgear com ...