RUGGEDCOM RST2228
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests
43
Test
Description
Test Levels
Severity Levels
IEC 60068-2-14
Change of Temperature
Test Nb
5 Cycles, -40 to 85°
C (40 to 185° F)
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
93% upper temperature,
97% lower temperature
55 °C (131 °F), 6 Cycles
IEC 60068-2-78
Humidity (Damp
Heat, Steady State)
Test Cab
10 days @ 55 °C (131 °F)
and 93% Relative Humidity
IEC 60255-21-1
Vibration
Level 2 (2 g @ 10 to 150 Hz)
Class 2
Shock
Level 2 (30 g @ 11 mS)
Class 2
IEC 60255-21-2
Bump
Level 1 (10 g @ 16 mS)
Class 1
IEC 60255-21-3
Seismic
Method A, Class 2
Class 2
IEC 60529
Ingress Protection
IP4x
IEC 60068-2-31
Free Fall
Test Ec
25 cm