LED_2 is always dark:
LED_2 lights always:
LED_2 flashes always:
LED_2 flashes briefly:
Reception of control telegram
7
Finish mounting of REV-R.03/1
a) Switch off power
b) Mark location where REV-R.03/1 is currently fixed
c)
If necessary loosen wiring
d) Mount receiver at location marked before according Fig. H to
M, wire completely and close housing
e) Switch on power
Commissioning the controller / transmitter REV23.03RF
1 Configuration
1.1 Accessing the heating engineer level
The heating engineer level will be enabled by pressing
simultaneously the warmer and colder buttons and by rolling the
roller selector away from the display and then toward the display
(also refer to Fig. G).
1.1.1 Calibrating the sensor
After activating the heating engineer level, the
CAL
symbol will flash.
When pressing the roller selector, the room temperature currently
measured flashes and can now be recalibrated by a maximum of
± 2 °C by rolling either toward the display or away from it. To store
the recalibration, press the roller selector (also refer to Fig.
).
1.1.2 Setpoint limitation
There are 2 setting choices available:
or
.
On the heating engineer level, change from the flashing
CAL
symbol to the setpoint limitation symbol by rolling toward the display
(also refer to Fig.
). Press to accept. 5...29 °C will flash (factory
setting). Press to accept or continue rolling. Setting 16...29 °C will
flash. Press to accept.
1.1.3 Optimum start control
On the heating engineer level, change from the flashing
CAL
symbol
to the optimum start control symbols
by rolling
twice toward the display (also refer to Figs.
and
). Press to
accept.
will flash (factory setting). Press to accept or
continue
rolling until you reach ¼, ½, 1 or optimization OFF
.
Press to accept.
1.1.4 Control mode
On the heating engineer level, change from the flashing
CAL
symbol to the symbols of the various control modes by rolling
several times toward the display (also refer to Fig.
). Press to
accept.
(factory setting) will flash. Press to accept or continue rolling
toward the display to select one of the following control modes:
,
PID 6, PID 12 or
. Press to accept the required
control mode.
A description of the different control modes is given below (also
refer to Fig.
).
Difficult controlled systems:
Proper on / off controller with a switching differential
of 0.5 C (factory setting).
Self-learning,
adaptive control:
Suited for all standard applications.
PID 12
Normal controlled systems:
For locations with normal temperature variations.
PID 6
Fast controlled systems:
For locations with significant temperature variations.
1.1.5 Periodic pump run
This function protects the pump against seizing during longer off
periods. Periodic pump run is activated for a minute every 24 hours
at 12:00 (when pump run is activated, the flame symbol
appears on the display).
On the heating engineer level, change from the flashing
CAL
symbol to the
symbol by rolling twice away from the display
(factory setting, periodic pump run off).
Press to accept.
will flash (factory setting). Press to accept or
continue rolling. The
symbol for periodic pump run on will flash.
Press to accept (also refer to Fig.
).
1.1.6 Heating / cooling mode
On the heating engineer level, change from the flashing
CAL
symbol to the heating / cooling symbols by rolling away from the
display.
Press to accept. The heating symbol will flash (factory setting).
Press to accept or continue rolling. The cooling symbol
will
flash. Press to accept (also refer to Fig.
).
1.1.7 Frost protection mode
Use operating mode selector to select symbol
(also refer to Fig.
). If the standard value of 5 °C need to be
changed, the frost protection setpoint
must be changed via
temperature menu
T
(refer to operating instructions).
2 Functional
check
a) Check the display. If there is no display, check the correct
fitting and function of the batteries
b) Comfort mode
c)
Select temperature menu
T
and adjust a temperature setpoint
of 29 °C (refer to operating instructions)
d) The relay must be energized within one minute, causing the
actuating device to operate. Flame symbol
will appear on
the display. If that is not the case:
•
Check actuating device and wiring
•
The room temperature is possibly above 29 °C
e) Reset setpoint temperature
to its initial value (standard
value 19 °C or individual setting)
f) Select the required operating mode
3 Reset
User-defined data:
Press the button behind the pin opening for at least one second:
this resets the user-specific settings to their default values (the
heating engineer settings will not be changed). The clock starts at
12:00. During the reset time, all sections of the display light up,
enabling them to be checked.
All user-defined data plus the heating engineer settings:
Press the button behind the pin opening together with the warmer
and colder buttons for at least one second.
After this reset, the
factory settings
will be reloaded (also refer to
section “Factory settings“ in the operating instructions).
4 Notes
•
The controler conforms to “Software Class A” and is for use in
“normal” pollution situation
•
REV23.03RF/SET is a set of units consisting of electric room
temperature controller/thermostat with a weekly timeswitch and
transmitter (REV23.03RF) and a RF receiver (REV-R.03/1)
Orange on
Orange off
Controlled device OFF
Orange on
Orange off
Controlled device ON
Orange on
Orange off
Learning mode active