83
TUTORBIT
COSMOGAS
Continued on the next page
6 - USE
Monday Start Stop
06:00 8:00
12:00 14:00
18:00 00:00
Setting the 3 operating time slots on Monday
, T
uesday
, W
ednesay
,Thursday and Friday
.
Installer
Off Reduced Comfort Precomfort
Cooling
Timer program
Installer
Saturday
S
ta
rt S
to
p
06:00 8:00
12:00 14:00
18:00 22:00
Setting the 3 operating time slots on Saturday and Monday
Installer
Zone2
Heating circuit 2 (submenu equal to Zone 1)
User
Zone3
Heating circuit 2 (submenu equal to Zone 1)
User
Zone4
Heating circuit 2 (submenu equal to Zone 1)
User
Zone5
Heating circuit 2 (submenu equal to Zone 1)
User
Anti-legionella
Anti-legionella setting parameters for the DHW tank
Installer
Frequence
Cycle frequency
Installer
1...30
7 days
Light-on hour
Cycle start time
Installer
0...23
6 h
Setpoint
Hot water tank filling setpoint during the anti-legionella cycle
Installer
50...70
65 °C
Max light-on delay
Maximum time for reaching the anti-legionella setpoint
Installer
1...360
30 min
Hold on timer
Minimum time for maintaining the anti-legionella temperature
Installer
1...360
15 min
Output rotation
Rotation of the heat generators
Installer
Heating
Rotation of the heat generators assigned to the “Heating” service
Installer
Mode
Type of rotation: Fixed = rotation on a time basis; Absent = no rotation; Timed = Rotation based on the ageing time;
Installer
Fixed; Absent; Timed;
Fixed
Fix Rotation
“Fix rotation” parameters
Installer
Interval
Time for the next rotation
Installer
0...15
6 days
Base time rotation
“Base time rotation” parameters
Installer
Max ancient dif
f
Maximum ageing time of a heat generator after which rotation occurs.
Installer
0...10
6 days
DHW
Rotation of the heat generators assigned to the “DHW” service
Installer
Mode
Type of rotation: Fixed = rotation on a time basis; Absent = no rotation; Timed = Rotation based on the ageing time;
Installer
Fixed; Absent; Timed;
Fixed
Fix Rotation
“Fix rotation” parameters
Installer
Interval
Time for the next rotation
Installer
0...15
6 days
Base time rotation
“Base time rotation” parameters
Installer
Max ancient dif
f
Maximum ageing time of a heat generator after which rotation occurs.
Installer
0...10
6 days
Outdoor temperature
Outdoor sensor parameters
Installer
Building type
Delay generated by the building’
s insulation before an external temperature variation af
fects the room
temperature
Installer
0...20
0 hs
Actual
Actual outdoor temperature
Installer
Value
Value
Summary of Contents for POL955
Page 31: ...31 TUTORBIT COSMOGAS Figure 4 14 Electrical connection 4 INSTALLATION ...
Page 33: ...33 TUTORBIT COSMOGAS Figure 4 16 Electrical connections 4 INSTALLATION ...
Page 35: ...35 TUTORBIT COSMOGAS Figure 4 18 Electrical connections 4 INSTALLATION ...
Page 37: ...37 TUTORBIT COSMOGAS Figure 4 20 Electrical connection 4 INSTALLATION ...
Page 39: ...39 TUTORBIT COSMOGAS Figure 4 22 Electrical connection 4 INSTALLATION ...
Page 41: ...41 TUTORBIT COSMOGAS Figure 4 24 Electrical connection 4 INSTALLATION ...
Page 43: ...43 TUTORBIT COSMOGAS Figure 4 26 Electrical connection 4 INSTALLATION ...
Page 45: ...45 TUTORBIT COSMOGAS Figure 4 28 Electrical connection 4 INSTALLATION ...
Page 47: ...47 TUTORBIT COSMOGAS Figure 4 30 Electrical connection 4 INSTALLATION ...
Page 49: ...49 TUTORBIT COSMOGAS Figure 4 32 Electrical connection 4 INSTALLATION ...
Page 51: ...51 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 34 Electrical connection ...
Page 53: ...53 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 36 Electrical connection ...
Page 54: ...54 TUTORBIT COSMOGAS 4 INSTALLATION ...
Page 57: ...57 TUTORBIT COSMOGAS Figure 4 38 Electrical connection 4 INSTALLATION ...
Page 59: ...59 TUTORBIT COSMOGAS Figure 4 40 Electrical connection 4 INSTALLATION ...
Page 61: ...61 TUTORBIT COSMOGAS Figure 4 42 Electrical connection 4 INSTALLATION ...
Page 96: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...