64
TUTORBIT
COSMOGAS
5 - ALARMS AND DIAGNOSTICS
A015 Anti-stagnation : Alarm;
Solar circuit Anti-stagnation alarm;
a.- Check actual solar circuit
temperature;
b.- Check the state of the solar probe;
a.- Wait for the temperature
to drop;
b.- Replace the solar probe;
A016- Sp 0-10V external : Low limit alarm;
Low communication signal alarm (< 0V); Check the signal voltage;
Increase the value of the
0-10V >0V signal;
A016- Sp 0-10V external : High limit alarm;
High communication signal alarm
(> 12V);
Check the signal voltage;
Reduce the value of the
0-10V <12V signal;
A017 Input/output forcing : Warning;
An input / output has been forced in
manual mode;
Reset automatic mode;
A018 External T.Probe Not Configured :
Alarm;
External probe not configured;
Check that the external probe is active;
Activate the external probe;
A019 Solar panel probe : ShortLoop
Probe in short circuit;
Check if the probe is in short circuit;
Replace the probe;
A019 Solar panel probe : noSensor /
openLoop;
Probe Circuit open;
Check probe connection;
Restore the connection;
A020 Anti-legionella alarm : Alarm;
Anti-legionella cycle not completed;
a.- Make sure the hot water tank probe
is in the correct position;
b.- Make sure the flow rate is correct
between the hot water tank and the heat
generator;
a.- Restore the probe
position;
b.- Restore the correct flow
rate;
A021 Antileg:No Solar & Mix. pump
Mixing pump configured for anti-
legionella and solar is not enabled;
Enable solar;
A022 Recirculation Temperature Probe :
ShortLoop
Probe in short circuit;
Check if the probe is in short circuit;
Replace the probe;
A022 Recirculation Temperature Probe :
noSensor / openLoop;
Probe Circuit open;
Check probe connection;
Restore the connection;
A023 Mixing Pump : CommFault;
Communication error;
Check Expansion connection;
Restore the connection;
A024 Circ3 3pt Open : CommFault;
Communication error;
Check Expansion connection;
Restore the connection;
A025 Circuit 3 pump : CommFault;
Communication error;
Check Expansion connection;
Restore the connection;
A026 Circ3 3pt Close : CommFault;
Communication error;
Check Expansion connection;
Restore the connection;
A030 Gener. 1 Burner 1
Module 1 error alarm;
Check the type of error on the generator
1 display;
Restore by following the
instructions provided with
the generator;
A031 Gener. 1 Burner 2
Module 1 error alarm;
Check the type of error on the generator
1 display;
Restore by following the
instructions provided with
the generator;
A032 Gener. 1 Burner 3
Module 1 error alarm;
Check the type of error on the generator
1 display;
Restore by following the
instructions provided with
the generator;
A033 Gener. 1 Burner 4
Module 1 error alarm;
Check the type of error on the generator
1 display;
Restore by following the
instructions provided with
the generator;
A034 Gener. 2 Burner 1
Module 2 error alarm;
Check the type of error on the generator
2 display;
Restore by following the
instructions provided with
the generator;
A035 Gener. 2 Burner 2
Module 2 error alarm;
Check the type of error on the generator
2 display;
Restore by following the
instructions provided with
the generator;
A036 Gener. 2 Burner 3
Module 2 error alarm;
Check the type of error on the generator
2 display;
Restore by following the
instructions provided with
the generator;
A037 Gener. 2 Burner 4
Module 2 error alarm;
Check the type of error on the generator
2 display;
Restore by following the
instructions provided with
the generator;
A038 Gener. 3 Burner 1
Module 3 error alarm;
Check the type of error on the generator
3 display;
Restore by following the
instructions provided with
the generator;
A039 Gener. 3 Burner 2
Module 3 error alarm;
Check the type of error on the generator
3 display;
Restore by following the
instructions provided with
the generator;
Summary of Contents for POL955
Page 31: ...31 TUTORBIT COSMOGAS Figure 4 14 Electrical connection 4 INSTALLATION ...
Page 33: ...33 TUTORBIT COSMOGAS Figure 4 16 Electrical connections 4 INSTALLATION ...
Page 35: ...35 TUTORBIT COSMOGAS Figure 4 18 Electrical connections 4 INSTALLATION ...
Page 37: ...37 TUTORBIT COSMOGAS Figure 4 20 Electrical connection 4 INSTALLATION ...
Page 39: ...39 TUTORBIT COSMOGAS Figure 4 22 Electrical connection 4 INSTALLATION ...
Page 41: ...41 TUTORBIT COSMOGAS Figure 4 24 Electrical connection 4 INSTALLATION ...
Page 43: ...43 TUTORBIT COSMOGAS Figure 4 26 Electrical connection 4 INSTALLATION ...
Page 45: ...45 TUTORBIT COSMOGAS Figure 4 28 Electrical connection 4 INSTALLATION ...
Page 47: ...47 TUTORBIT COSMOGAS Figure 4 30 Electrical connection 4 INSTALLATION ...
Page 49: ...49 TUTORBIT COSMOGAS Figure 4 32 Electrical connection 4 INSTALLATION ...
Page 51: ...51 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 34 Electrical connection ...
Page 53: ...53 TUTORBIT COSMOGAS 4 INSTALLATION Figure 4 36 Electrical connection ...
Page 54: ...54 TUTORBIT COSMOGAS 4 INSTALLATION ...
Page 57: ...57 TUTORBIT COSMOGAS Figure 4 38 Electrical connection 4 INSTALLATION ...
Page 59: ...59 TUTORBIT COSMOGAS Figure 4 40 Electrical connection 4 INSTALLATION ...
Page 61: ...61 TUTORBIT COSMOGAS Figure 4 42 Electrical connection 4 INSTALLATION ...
Page 96: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com ...