B-4
Manual OP5, OP15
( ) J31069-D0840-U001-A2-7618
Action
Cause
Message
$ 135
Mode change
$ 200
Backup battery voltage has fallen
below minimum value or:
wrong battery type inserted
Replace battery
$ 201
Error during clock chip write (hard-
ware error)
Return device for repair
$ 202
Error when reading date
Re-enter date (return OP for repair)
$ 203
Error when reading time
Re-enter time (return OP for repair)
$ 204
Error when reading day
Re-enter day (return OP for repair)
$ 205
Printer not ready and internal stor-
age of print jobs is no longer pos-
sible (capacity exceeded)
Ready printer or disable message log
$ 206
Printer not ready, print job will be
stored temporarily
Ready printer
$ 207
Print job was aborted
Check printer, cable and connector
$ 210
Internal error
Refer to Action for internal errors
$ 212
Internal error
Refer to Action for internal errors
$ 213
Offline mode not possible at present
Try mode change again later
$ 214
The job number sent by PLC is too
high
Check PLC-user program
$ 217
$ 218
The addresses of two variables
overlap
Modify configuration
(variable)
$ 220
$ 221
Printer buffer overflowed, messages
have been lost
$ 222
Event buffer full to remaining
buffer space
Delete buffer or configure smaller remaining
buffer space
$ 224
Event buffer full; buffer partially
deleted and forced printout initiated
$ 225
Alarm buffer full to remaining
buffer space
Delete buffer or configure smaller remaining
buffer space
$ 227
Alarm buffer full; buffer partially
deleted and forced printout initiated
$ 229
Keyboard connector faulty or loose
(hardware fault)
Return device for repair
System Messages
Summary of Contents for OP15
Page 6: ...iv Manual OP5 OP15 J31069 D0840 U001 A2 7618 Preface ...
Page 11: ...Product Description 1 Functionality 2 Part I Introduction ...
Page 12: ... 2 Manual OP5 OP15 J31069 D0840 U001 A2 7618 ...
Page 24: ...2 4 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Functionality ...
Page 26: ... 2 Manual OP5 OP15 J31069 D0840 U001 A2 7618 ...
Page 42: ...4 10 Manual OP5 OP15 J31069 D0840 U001 A2 7618 General Operation ...
Page 66: ...7 16 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Message Handling ...
Page 78: ...8 12 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Recipes ...
Page 88: ... 2 Manual OP5 OP15 J31069 D0840 U001 A2 7618 ...
Page 98: ... 2 Manual OP5 OP15 J31069 D0840 U001 A2 7618 ...
Page 122: ...17 8 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Device Description ...
Page 128: ...19 4 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Test and Monitoring Functions ...
Page 132: ... 2 Manual OP5 OP15 J31069 D0840 U001 A2 7618 ...
Page 146: ...B 12 Manual OP5 OP15 J31069 D0840 U001 A2 7618 System Messages ...
Page 150: ...C 4 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Technical Data ...
Page 156: ...E 4 Manual OP5 OP15 J31069 D0840 U001 A2 7618 ESD Guidelines ...
Page 165: ...F 9 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Siemens Worldwide ...
Page 177: ...Index 8 Manual OP5 OP15 J31069 D0840 U001 A2 7618 Index ...