Maintenance / Repair
Testing the point detector
7
98 | 108
Building Technologies
A6V10305793_m_en_--
Fire Safety
2016-02-15
7.2.4 Testing the functionality of the 'Technical Ambient
Supervision Message'
You do not have to check the functionality of the 'Technical Ambient Supervision
Message' on a regular basis.
Testing the fire detection functionality and the CO functionality ensures that the
'Technical Ambient Supervision Message' is also working.
7.2.4.1 'Technical Ambient Supervision Message' performance
check
You cannot test whether the 'Technical Ambient Supervision Message' is
functioning correctly with test devices.
Checking can only take place indirectly:
w
You must know the current ambient temperature.
l
Enter the following parameters in the 'Cerberus-Engineering-Tool' software:
– A hysteresis range of 5 °C.
– A temperature threshold which is at least 10 °C below the current ambient
temperature.
– Alarming when value falls below threshold
a
The detector sends a signal to the control panel.
a
The 'Technical Ambient Supervision Message' is working correctly if the control
panel displays the corresponding message.