Structure and function
Accessories
3
50 | 108
Building Technologies
A6V10305793_m_en_--
Fire Safety
2016-02-15
3.5.14 Micro terminal DBZ1190-AA
●
Auxiliary terminal for connecting cables
●
For T-branches of additional cabling e.g. for detector
heating units, sounder base, external alarm indicators etc.
●
For wire diameters of 0.28…0.5 mm
2
●
4-pin
●
Order no.: BPZ:4677080001
3.5.15 Connection terminal DBZ1190-AB
●
Auxiliary terminal for connecting cables
●
For T-branches of additional cabling, e.g., for cable
shielding, detector heating units, sounder base, external
alarm indicators, etc.
●
For wire diameters of 1…2.5 mm²
●
3 poles
●
Order no.: BPZ:4942340001
3.5.16 Parameter set resistor 33 k
Ω
PSR720-1
●
For selecting the 'Suppression' parameter on a point
detector OOH740 in collective mode
●
Resistance value: 33 k
Ω
●
Install the resistors directly in a detector base DB721D or
detector base (collective) DB110 between terminals '5'
and '1a'
●
Compatible with:
–
Multi-sensor smoke detector, ASA OOH740
●
Order no.: S54319-F16-A1
See also
2
Connection diagram, collective [
3.5.17 Parameter set resistance 68 k
Ω
PSR720-2
●
For selecting the 'High Sensitive Fast' parameter set on a
point detector OOH740 in collective mode
●
Resistance value: 68 k
Ω
●
Install the resistors directly in a detector base DB721D or
detector base (collective) DB110 between terminals '5'
and '1a'
●
Compatible with:
–
Multi-sensor smoke detector, ASA OOH740
●
Order no.: S54319-F17-A1
See also
2