Planning
Fire detection
4
59 | 108
Building Technologies
A6V10305793_m_en_--
Fire Safety
2016-02-15
4.2.4.2 Use
No.
Name
Risk of damage to
persons
Concentration of
valuable items
Room geometry Deceptive
phenomena
Risk of fire
Critical fire size
small …
large
low …
high
simple …
complex
few …
many
small …
large
small …
medium
2
'Robust'
1
'Universal'
3
'Sensitive'
5
'Super Sensitive'
6
'Ultra Sensitive'
4.2.4.3 Specification
The table below shows the parameter sets' characteristics and fields of application:
No.
Name
Response time
[s]
Sensitivity
open fire/smoldering fire
[%/m]
0
'Universal'
50
2.3 / 8
2
'Robust'
80
2.3 / 8
1
'Universal'
50
2.3 / 8
3
'Sensitive'
30
1.6 / 5.6
5
1
'Super Sensitive' 12
1.0 / 1.5
6
1
'Ultra
Sensitive' 12
0.35 / 0.5
1
Only in the OOH740 from ES
≥
20