Fire detection
4
54 | 108
Building Technologies
A6V10305793_m_en_--
Fire Safety
2016-02-15
Balanced CO (10):
This parameter set displays a balanced response behavior in its response to fires
and robustness to deceptive phenomena. It reacts faster with open fires. It reacts
slower with vapor and cigarette smoke. In the event of smoldering fires or fires in
cleaning rooms, the parameter set reacts quicker than the 'Balanced (4)' parameter
set as it takes the CO concentration into account.
Thanks to the fact that three criteria are evaluated (smoke, heat and CO
concentration), this gives particular robustness to deceptive phenomena when
compared with more sensitive parameter sets.
Fast Response (6):
This parameter set reacts in a fast and highly sensitive manner. It is thus especially
suitable for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
High Sensitive Fast (9):
This parameter set is suited for applications requiring very high sensitivity levels. It
reveals a significantly higher optical and thermal sensitivity than 'Fast Response'.
This parameter set is also suited for applications that can otherwise only be
covered with special detectors.
Super Sensitive (11):
This parameter set can be selected for all point detectors OOH740 from product
version ES
≥
20.
The parameter set is suitable for applications that require fast and sensitive
response behavior. It is twice as sensitive as 'High Sensitive Fast' in detecting
smoldering fires and temperature increases. Its response behavior with respect to
smoldering fires is similar to that of the 'Sensitive' parameter set.
Download 1 (14) / download 2 (15):
Application-specific parameter sets that can be loaded directly onto the point
detector.
All parameter sets except for 8 comply with standards EN 54-7 and CEA 4021.
Parameter sets 'Balanced CO' and 'Suppression CO' do not have LPCB approval.