Mounting / Installation
Detector base DB72x and detector base (collective) DB110
5
74 | 108
Building Technologies
A6V10305793_m_en_--
Fire Safety
2016-02-15
5.2 Detector base DB72x and detector base (collective)
DB110
●
Install the detector base DB72x or DB110 directly on the ceiling.
●
Insert the cables into the detector base. You have the option of using the
following types of line:
– Recess-mounted cable entry
– Surface-mounted cable entry (cable diameter max. 8 mm)
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
●
The cable loops must be placed flat in the base bottom.
●
The bare length of the cables is approximately 8…10 mm.
1
Minimum Ø 40 mm
2
Maximum Ø 90 mm
Please note the limitations when using the detector base DB721D.
See chapter 'Connection diagram, collective [
87]'.
In the case of the detector bases DB721 and DB722, the C-NET detector line is
not interrupted even if a point detector is not used.
Only use the detector base DB110 on collective detector lines.
1
2