Mounting / Installation
Detector base seal RS720
5
77 | 108
Building Technologies
A6V10305793_m_en_--
Fire Safety
2016-02-15
5.4 Detector base seal RS720
●
Use the detector base seal RS720 to install point detectors in wet rooms.
Protection category: IP42.
●
Compatible with the detector bases DB72x, the detector base (collective)
DB110 and the sounder base DBS720.
●
Only use for recess-mounted cable entry.
Installing the detector base seal
1.
NOTICE! Excessively large holes in the detector base seal will impair the
potential IP protection category. Do not cut or drill holes in the detector base
seal. Without using a tool, push the lines through the detector base seal.
2. Fit the detector base seal RS720 between the ceiling and the detector base or
the sounder base.
Figure 12: Installing the detector base seal RS720