Communication and delivery of alarms
15.07.2005
To ensure the required functionality, contact the telephone
provider for the available protocols and the concrete phone
numbers.
Subsection “5.3.2 Selection of modem and provider“ gives an
overview of the available choices in terms of modem tech-
nology and protocols. For selected countries, a list of the ac-
cess numbers to be set on operating page “Phone numbers“
is given. Subsection “5.3.3 Operating page “Modem“ “ de-
scribes the required configuration of the modem.
In section “5.4 Sending alarms“, the software settings re-
quired for the different alarm choices are described in a
number of steps.
5.3.2 Selection of modem and provider
The following overview helps prevent mistakes when select-
ing the modem and the provider.
OCI600
with…
Application analog
modem
1)
ISDN modem
1)
GSM
modem
1)
Connection to
ACS7... with
PC modem
type…
•
Analog
1)
•
GSM
1)
Only:
ISDN
•
GSM
1)
•
Analog
1)
Alerting via
SMS
UCP (TAP for
SMS) provider
service
UCP (TAP for
SMS) provider
service
UCP (TAP for
SMS) provider
service
Alerting via
pager
TAP provider
service
TAP provider
service
TAP provider
service
Alerting via
fax
Modem must
support “Group 2
fax protocol“
2)
Not possible
because ISDN
fax machines are
not commercially
available
Modem must
support “Group 2
fax protocol“
2)
1)
HAYES-compatible to one another
2)
Modern fax machines should be downward-compatible and still support the “Group 3 fax
protocol“