Page 52
Milltronics BW100 - INSTRUCTION MANUAL
7ML19985DJ01
mmmm
m
Pa
ra
m
et
er
s
P018 Speed Constant Adjust
This parameter allows adjustment to the speed constant (P015).
Initially, this parameter displays the dynamic speed of the belt. If the displayed speed is
not equal to the actual speed, enter the actual belt speed.
For speed sensor applications, the value of P015 is automatically adjusted.
For constant speed (TB1 5/6 jumper) the value of P014 is automatically adjusted.
P019 Manual Span Adjust
This parameter allows adjustment to the span calibration.
The adjustment value is generally determined by performing material tests. Refer to
Recalibration/Material Tests,
page 30.
Enter the calculated adjustment.
P022 Minimum Speed Frequency
Sets the minimum frequency that the speed sensor can reliably read. Signals at low
frequencies are erratic, adversely affecting the performance of the weighing system.
Entry:
1 = 1 Hz (at 1 Hz, it takes 1 sec before defaulting to 0 speed)
2 = 2 Hz (at 2 Hz, it takes 0.5 sec before defaulting to 0 speed)
P080 Damping
Sets the speed of response to which the displayed readings (rate, load and speed), and
outputs (alarm and mA) react to change.
The greater the damping value, the slower the response.
Enter damping value, range 1 - 9999.
P081 Display Mode
Sets the display mode. Normally, the display shows rate, or the last manually selected
function. If set to alternating, the display alternates between rate and totalizer (1 and/or
2, as programmed by P647).
Entry:
0 = normal
1 = alternating
Note:
The effect of damping (P080) on mA output can be overridden by mA output
damping (P220).