Milltronics BW100 - INSTRUCTION MANUAL
7ML19985DJ01
mmmm
m
Co
mmun
icat
io
ns
Parameters
P000 Security lock
Locks out the programming change value function such that the values of P001 through
P999 cannot be changed. This however does not prevent the select function from use; i.e.
for viewing values.
Programming is locked out if the value of P000 is other than 1954.
Entry:
1954 = unlocked
f
1954 = locked
Quick Start (P005 to P017)
P005 Design Rate Units
Determines the units for programming and measurement.
Entry:
1
f
=
t/hr (tonnes per hour)
2 = kg/hr (kilograms per hour)
3 = LT/Hr (long tons per hour)
4 = T/h (short tons per hour)
5 = lb/hr (pounds per hour)
Changing this parameter does not affect the rate (P011), belt speed (P014) or belt length
(P016) parameters. These parameters should be re-entered for conformity in units.
t = 1000 kg
LT = 2240 lb.
T = 2000 lb.
P011 Design Rate
Specifies the design rate of material flow for the belt scale.
Enter the design rate from the supplied design data sheet
Note:
f
denotes factory default.
Note:
Quick Start is the minimum parameter programming required before
attempting a calibration and successful entry into the RUN mode.