Issue 10/06
9 Electro-magnetic compatibility (EMC)
MICROMASTER 430 Operating Instructions
6SE6400-5AE00-0BP0
91
9.1.5
Classification of EMC performance
Three General classes of EMC performance are available as detailed below:
Class 1: General Industrial
Compliance with European Standard EN 61800-3 (EMC Product Standard for
Power Drive Systems) for use in
Second Environment (Industrial)
.
Table 9-1
General Industrial
EMC Phenomenon
Standard
Level
Radiated Emissions
EN 55011
Level A1
Emissions:
Leitungsgebundene
Emissionen
EN 61800-3
Limits complying with EN 55011,
Class A, Group 2
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
2 kV power cables, 1 kV control
Immunity:
Radio Frequency
Electromagnetic Field
EN 61000-4-3
26-1000 MHz, 10 V/m
Class 2: Filtered Industrial
This level of performance will allow the manufacturer/assembler to self-certify their
apparatus for compliance with the EMC directive for the industrial environment as
regards the EMC performance characteristics of the power drive system.
Performance limits are as specified in the Generic Industrial Emissions and
Immunity standards EN 50081-2 and EN 50082-2.
Table 9-2
Filtered Industrial
EMC Phenomenon
Standard
Level
Radiated Emissions
EN 55011
Limit A1
Emissions:
Conducted Emissions
EN 61800-3
Limits complying with EN 55011,
Class A, Group 2
Supply Voltage Distortion
EN 61000-2-4
Voltage Fluctuations, Dips,
Unbalance, Frequency
Variations
EN 61000-2-1
Magnetic Fields
EN 61000-4-8
50 Hz, 30 A/m
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
2 kV power cables, 2 kV control
Radio Frequency
Electromagnetic Field,
amplitude modulated
EN 61000-4-3
80-1000 MHz, 10 V/m, 80% AM,
power and signal lines
Immunity:
Radio-frequency
Electromagnetic Field,
pulse modulated
EN 61000-4-3
900 MHz, 10 V/m 50% duty cycle,
200 Hz repetition rate
http://nicontrols.com