MICROMASTER 430 specifications
Issue 10/06
MICROMASTER 430 Operating Instructions
84
6SE6400-5AE00-0BP0
Input voltage range
3 AC 380 V … 480 V, ± 10 %
(Unfiltered)
Order No.
6SE6430-
2UD27-
5CA0
2UD31-
1CA0
2UD31-
5CA0
2UD31-
8DA0
2UD32-
2DA0
2UD33-
0DA0
[kW] 7,5
11,0
15,0
18,5
22,0
30,0
VT Motor Output Rating
[hp] 10,0
15,0
20,0
25,0
30,0
40,0
Output Power
[kVA]
10,1
14,0
19,8
24,4 29,0
34,3
VT Input Current 1)
[A]
17,3
23,1
33,8
37,0 43,0
59
VT Output Cur. Max.
[A]
19,0
26,0
32,0
38,0 45,0
62,0
[A]
20 32 35 50 63
80
Recommended Fuse
3NA
3807 3812 3814 3820 3822
3824
[A]
50
63
80
Fuses recomnended for
UL applications
3NE
* * *
1817-0 1818-0
1820-0
[mm
2
] 2,5
4,0
6,0
10,0
10,0
16,0
Input Cable Min.
[AWG] 14 12 10 8 8
6
[mm
2
] 10,0
10,0
10,0
35,0
35,0
35,0
Input Cable Max.
[AWG] 8 8 8 2 2
2
[mm
2
] 2,5
4,0
6,0
10,0
10,0
16,0
Output Cable Min.
[AWG] 14 12 10 8 8
6
[mm
2
] 10,0
10,0
10,0
35,0
35,0
35,0
Output Cable Max.
[AWG] 8 8 8 2 2
2
Frame Size
C D
[kg] 5,5
5,5
5,5
16,0
16,0
16,0
Weight
[lbs] 12,1
12,1
12,1
35,0
35,0
35,0
Order No.
6SE6430-
2UD33-
7EA0
2UD34-
5EA0
2UD35-
5FA0
2UD37-
5FA0
2UD38-
8FA0
[kW] 37,0
45,0 55,0 75,0 90,0
VT Motor Output Rating
[hp]
50,0 60,0 75,0 100,0 120,0
Output Power
[kVA]
47,3
57,2 68,6 83,8 110,5
VT Input Current 1)
[A]
72 87 104 139 169
VT Output Cur. Max.
[A]
75,0 90,0 110,0 145,0 178,0
[A] 100
125 160 160 200
Recommended Fuse
3NA 3830
3832 3836 3140 3144
[A] 100
125 160 200 200
Fuses recomnended for
UL applications
3NE 1021-0
1022-0 1224-0 1225-0 1227-0
[mm
2
] 25,0
25,0 35,0 70,0 70,0
Input Cable Min.
[AWG]
3
3 2 2/0
2/0
[mm
2
] 35,0 35,0 150,0 150,0 150,0
Input Cable Max.
[AWG] 2 2 300 300 300
[mm
2
] 25,0
25,0 35,0 70,0 95,0
Output Cable Min.
[AWG]
3
3 2 2/0
4/0
[mm
2
] 35,0 35,0 150,0 150,0 150,0
Output Cable Max.
[AWG] 2 2 300 300 300
Frame Size
E F
[kg]
20,0
20,0 56,0 56,0 56,0
Weight
[lbs]
44,0 44,0 123,0 123,0 123,0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 400 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America