![Siemens MICROMASTER 430 Operating Instructions Manual Download Page 56](http://html.mh-extra.com/html/siemens/micromaster-430/micromaster-430_operating-instructions-manual_377234056.webp)
Issue 10/06
3 Commissioning
MICROMASTER 430 Operating Instructions
6SE6400-5AE00-0BP0
55
Flow chart Quick Commissioning
P0010 Start Quick Commissioning
2)
0
Ready to Run
1
Quick Commissioning
30 Factory Setting
P0100 Operation for Europe/N. America
0
Power in kW; f default 50 Hz
1
Power in hp; f default 60 Hz
2
Power in kW; f default 60 Hz
NOTE
Settings 0 and 1 should be changed using the DIP
switches to allow permanent setting. The DIP
switches should be used to create permanent
settings. After a mains break the DIP switch settings
overide the parameter settings.
P0304 Rated Motor Voltage
1)
Setting range: 10 V - 2000 V
Nominal motor voltage (V) from rating plate.
P0307 Rated Motor Power
1)
Setting range: 0,01 kW - 2000 kW
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp.
P0308 Rated motor cosPhi
1)
Setting range: 0,000 - 1,000
Nom. motor power factor (cosPhi) from rating plate .
Visible only when P0100 = 0, 2, (motor power in kW).
P0309 Rated motor efficiency
1)
Setting range: 0,0 - 99,9 %
Nominal motor efficiency in % from rating plate. .
Visible only when P0100 = 1, ( motor power in hp).
P0310 Rated Motor Frequency
1)
Setting range: 12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate.
P0311 Rated Motor Speed
1)
Setting range: 0 - 40.000 U/min
Nominal motor speed (rpm) from rating plate.
P0320 Motor magnetizing current
Setting range: 0.0 - 99.0 %
Motor magnetizing current (%) relative to the rated
motor current (P0305).
P0335 Motor cooling
0
Self-cooled
1
Force-cooled
2 Self-cooled and internal fan
3 Force-cooled and internal fan
P0640 Motor overload factor
Setting range: 10.0 - 400.0 %
Motor overload current limit [%] relative to P0305
(rated motor current).
1
Access level
1
1
3
P0305 Rated Motor Current
1)
Setting range: 0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate.
1
3
3
1
1
2
1
1
P0700 Selection of Command Source
2)
0
Factory Setting
1
BOP-2
2
Terminals (Digital Inputs)
1
Note
If P0700 = 2 is selected, the function of the digital
inputs can be determind via P0701 to P0708. P0701
to P0708 = 99 enables the BICO-parameterization for
the digital inputs.
P0003 User access level
2)
1
Standard
2
Extended
3
Expert
1
P0500 Technological application
0
Constant torque
1
Pumps and fans
3
1) Motor-specific parameters – see motor rating plate.