Issue 10/06
4 MICROMASTER 430 functions
MICROMASTER 430 Operating Instructions
6SE6400-5AE00-0BP0
63
4.1
Frequency set point (P1000)
¾
Pre-setting:
terminal 3/4 (AIN+/ AIN -, 0…10 V equivates to
0…50/60 Hz)
¾
Additional
settings:
see
P1000
4.2
Command sources (P0700)
ATTENTION
The
ramp-up /ramp-down times
and r
amp smoothing
also have an effect on the
motor’s start and stop behaviour. Further details about these functions are to be
found in the parameter list for parameters P1120, P1121, P1130 – P1134.
Start motor
¾
Default:
terminal 5 (DIN1, high)
¾
Additional settings:
see P0700 to P0708
Stop motor
¾
There are a number of possibilities to stop the motor:
¾
Default
:
♦
OFF1
terminal 5 (DIN1, low)
♦
OFF2
OFF key on BOP-2, press the OFF key once for 2
seconds or press twice
♦
OFF3
not active in factory settings
¾
Additional settings:
see P0700 to P0708
Reversing the direction of rotation of the motor
This function is inhibited in the factory settings. To release it, you must set
P1110 = 0.
¾
Default:
terminal 6 (DIN2, high)
¾
Additional settings:
see P0700 to P0708