3 Commissioning
Issue 10/06
MICROMASTER 430 Operating Instructions
50
6SE6400-5AE00-0BP0
3.2.2 Commission
Overview with BOP-2
Prerequisites
Mechanical and electrical Installation are completed.
NOTES
We recommend the commissioning according this scheme.
Setting the motor frequency
DIP Switch 2: OFF = 50 Hz / ON = 60 Hz
Quick Commissioning P0010 = 1
See Section 3.2.3.1
Further Commissioning via P0004 and P0003
An overview of the parameter structure is given in
Section 5.1
For a detailed description of the parameter, see the
Parameter List.
Power ON