Diagnostics and maintenance
5.4 Upload tp PG/Upload from device
IE/PB LINK PN IO
Operating Instructions, 11/2017, C79000-G8976-C393-02
73
5.4
Upload tp PG/Upload from device
Uploading from the device (STEP 7)
If you want to upload the configuration data from the device to the PG or engineering station,
in the selection dialog you need to set the rack to 0 and the slot to 0 or 2.
5.5
Replacing a module
5.5.1
Resetting address data
Note
Resetting address data if the use of the LINK is changed
If the LINK has already been operated in your plant and you want to use it at a different
location in the plant, it starts up with the configured parameters.
If the LINK has been used previously in your plant or has been repaired, delete all stored
data by resetting to the factory settings.
The MAC address is stored permanently on the LINK and is not deleted when you reset to
the factory settings.
5.5.2
Replacing older modules
Replacing a module
The LINK (6GK1 411-5AB10) can be used as a replacement for the following predecessor
products:
●
6GK1 411-5AB00