Service Manual
4-185
Installation
Protective power outage relays
●
For an indoor environment, use a safety ground conductor (PE) with a cross-section larger
than 2.5 mm
2
. For an outdoor environment, use a safety ground conductor (PE) with a
cross-section larger than 4 mm
2
.
●
The wire insulation should be color-coded yellow and green.
●
The grounding system’s impedance must not exceed 10 Ohms.
When uninstalling the system, the safety ground wire (PE) should be the last one disconnected.
The ground wire connection does not preclude the need to provide functional grounding to the
system using an appropriate power supply circuit (See “Power Systems” on page 2-26)
.
Checking the protective ground connection
Procedure
To ensure a proper grounding connection perform the tests described in the table below before
placing the system in service
.
4.15
Protective power outage relays
Each external analog line on the EB 202/204/206/210 modules features a relay that forwards
the line to the first two extension slots on each EB module in the event of a power outage.
The ground wire must be connected to the protective ground of the building, never
to water pipes, lightning rods, etc.
Step
Procedure
Result
(Rated Value)
1.
Measure the ohmic resistance between the ground
connection and the grounding bar.
< 1 Ohm
2.
Measure the ohmic resistance between the network’s
protective earth ground (PE) and the outlet or the
Main Distribution Frame.
< 1 Ohm
3.
Measure the ohmic resistance of the outlet’s neutral
conductor in relation to the earth.
< 10 Ohm
Expansion modules EB 200/400/800 do not feature protective relays.
Summary of Contents for HiPath 1100
Page 1: ...HiPath 1100 HiPath 1120 HiPath 1150 HiPath 1190 Service Manual ...
Page 14: ...Figures 14 Service Manual ...
Page 124: ...Modules 3 124 Service Manual Interconnect cables ...
Page 190: ...Installation 4 190 Service Manual Performing a visual inspection ...
Page 323: ...Service Manual 7 323 Operation Driver Installation Figure 7 44 Windows 2000 Driver location ...
Page 368: ...Operation 7 368 Service Manual HiPath 1100 applications ...
Page 384: ...Abbreviations 9 384 Service Manual ...
Page 388: ...388 Service Manual ...