4.6 Updating the firmware of the radio gateway
Only software packages created by Siemens are affected by the firmware update.
The following steps do not update the processor for line activation in the radio
gateway!
The firmware update is in a ZIP file. The DSV file version and the firmware
version must be compatible.
The radio gateway must be disconnected from the detector line or the detector
line is switched off prior to updating the radio gateway firmware.
The radio gateway is connected to the MCL-USB adapter (radio) FDUZ227 via
a cable.
The MCL-USB adapter (radio) FDUZ227 is connected to the PC via a USB
cable.
1. In the menu bar 'Network', select the relevant radio gateway.
2. In the menu bar 'Update', select the menu 'Update Gateway'.
3. Enter your password. The initial password is '1234'. Click on 'Next'.
Click on the 'Change password' button to set a new password.