4.4.5 Reading the report
The report contains the real data at the time of recording by the radio gateway.
Due to the dynamic performance of the radio system, the system adapts to
changes automatically. Consequently, the current data may differ from that
actually stored.
The radio gateway saves data from all the devices connected to it. This data
collection is only renewed every so often and may, therefore, be several months
old.
The following values can be read out:
Term
Explanation
Net ID:
Displays the ID of the network.
Device ID
Displays the serial ID of the device.
Device address
Displays the device address of the device. The device address consists of
'Zone customer text' and 'Logical channel customer text'.
Address
1
Displays the address of the device.
Device type name
Shows the device type as a symbol and the device designation.
Zone customer text
1
Displays the customer text of the group.
Logical channel customer
text
1
Displays the customer text for the channel address.
Hop count
Displays the number of radio links for this connection between the device and
radio gateway an.
Connectivity state
The connection status of this device is displayed.
Red 'No connection to gateway' There is no connection between the radio
gateway and the device.
Yellow 'Redundant path lost' The quality of the connection is good, but
there is only one path between the radio gateway and the device.
Dark green 'Good' The quality of the connection is very good; there are two
paths between the radio gateway and the device, with one path via a neighboring
device with the same number of radio links to the radio gateway.
Green 'Excellent' The quality of the connection is excellent; there are two
paths between the radio gateway and the device. Both paths go via neighboring
devices which are closer to the radio gateway.
Black 'Out of base' The device is not in the base/housing.