Operating Manual of FC18 Controller
Page: 27/70
9.
ACTIVATION/CONFIRMATION EVENT HANDLING
Activation status:
l
Activation indicator turns on (flashing if there is no confirmation)
l
Confirmation indicator turns on (only when confirmation signal is received)
l
The activation events are shown on the LCD as the figure
l
Acknowledge/Silence indicator flashing
l
Buzzer turns on
How to handle:
1.
Press “Acknowledge/Silence” to silence the buzzer:
l
Under Level 1 interface, a login interface pops out automatically. Enter
Level 2/3 password and press “OK” to return back to fire alarm window
then press “Acknowledge/Silence”. Now,
-
Buzzer is mute.
-
The “Acknowledge/Silence” indicator turns off.
l
Under Level 2/3 interface,
-
Buzzer is mute
-
The ”Acknowledge/Silence” indicator turns off.
2.
Find out the activation/confirmation location from LCD.
3.
Go to the site to handle it if necessary.
4.
Confirmation indicator turns off when confirmation signal disappears. When
activation signal disappears, press “Reset” to turn off the activation indicator
and the controller return to normal.
Note:
-
When an activation/confirmation event occurs together with another
event of higher priority, activation/confirmation event cannot be
displayed automatically. Enter the activation/confirmation window by
menu manually (see “real-time query” function) to handle it.
-
Press “
←
” to switch between alarm window and activation window
.
Fig.8-1activation interface