15
Siemens Building Technologies
Cerberus Division
E1481b
06.2000
5
Baud Rates
The following baud rates apply to the subsystems connected either to the CPU or the
expansion board.
SUBSYSTEM
SETTING
SUGGESTED BAUD RATE
CCTV Burle
compulsory
1200
CCTV Comerson
compulsory
4800
CDDL
suggested
4800
CERBAN
suggested
300
Cerloop
compulsory
1200 / 2400
CMX/CF9003
suggested
4800
LMS
suggested
9600
SEEP
suggested
4800
STT
compulsory
300
Two Level Network
suggested
4800
Cerpass
compulsory
9600
Size
compulsory
9600
Tab. 8 Subsystems suggested baud rate
BAUD RATE
UART
Spare
9600
4800
2400
1200
600
300
150
1
S1.7
ON
OFF
ON
OFF
ON
OFF
ON
OFF
S1.8
ON
ON
OFF
OFF
ON
ON
OFF
OFF
S2.1
ON
ON
ON
ON
OFF
OFF
OFF
OFF
2
S2.5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
S2.6
ON
ON
OFF
OFF
ON
ON
OFF
OFF
S2.7
ON
ON
ON
ON
OFF
OFF
OFF
OFF
3
S3.3
ON
OFF
ON
OFF
ON
OFF
ON
OFF
S3.4
ON
ON
OFF
OFF
ON
ON
OFF
OFF
S3.5
ON
ON
ON
ON
OFF
OFF
OFF
OFF
4
S4.2
ON
OFF
ON
OFF
ON
OFF
ON
OFF
S4.3
ON
ON
OFF
OFF
ON
ON
OFF
OFF
S4.4
ON
ON
ON
ON
OFF
OFF
OFF
OFF
5
S4.8
ON
OFF
ON
OFF
ON
OFF
ON
OFF
S5.1
ON
ON
OFF
OFF
ON
ON
OFF
OFF
S5.2
ON
ON
ON
ON
OFF
OFF
OFF
OFF
6
S5.6
ON
OFF
ON
OFF
ON
OFF
ON
OFF
S5.7
ON
ON
OFF
OFF
ON
ON
OFF
OFF
S5.8
ON
ON
ON
ON
OFF
OFF
OFF
OFF
Tab. 9 DIL-Switch settings for baud rate